Type : 2XY / A2XY / YJV

Voltage : 600 / 1000 V (permissible Service Voltage : 720 / 1200 V)

Special Type

  • 2XY(FP*)/2XY(FG*)
  • 2XY-FR/A2XY-FR
  • 2XY-FRLS/A2XY-FRLS
  • 2XY-LSZH/A2XY-LSZH
  • 2XY/A2XY-HRFR-150°

Specifications / Rating

ASTM: B-3
BDS IEC: 60228&60502-1
VDE: 0271
IEC: 60331&584
IS: 7098-1 & BS: 5467

Applications

  • Indoor
  • Outdoor
  • Underground
  • In water
  • Power plant
  • Switch gear
  • Generator
  • Industrial
  • Airport

Construction : Annealed Copper or Aleminium Conductor / XLPE Insulation / PVC inner Sheath / Black PVC outer sheath

tecnical data
Cross Sectional Area No. & Approx. Diameter of wire Cu/Al Nominal Thickness of Insulation Nominal Thickness of Sheath Overall diameter (approx) Approx Weight of Cable Max. DC resist. of conductor at 20°C Current rating at 30°C in ground Current rating at 35°C in air
Cu Al Cu Al Cu Al Cu Al
Core x mm2 No./mm mm mm mm Kg/Km Kg/Km ohm/km ohm/km amps amps amps amps
3x25rm+16rm 7/19 wire

7 wire
0.9

0.7
1.8 21.7 1110 637 0.717/1.15 1.2/1.91 130 94 120 96
3x35rm+16rm 19 wire

7 wire
0.9
0.7
1.8 24.0 1412 702 0.524/1.15 0.868/1.91 155 114 150 117
3x50rm+25rm 19 wire

7/19 wire
1.0
0.9
1.8 27.0 2035 946 0.387/0.727 0.641/1.20 190 133 190 142
3x70rm+35rm 19 wire

19 wire
1.1
0.9
1.9 30.5 2753 1201 0.286/0.524 0.443/0.868 225 164 230 179
3x95rm+50rm 19 wire

19 wire
1.1
1.0
2.1 34.9 3721 1553 0.193/0.387 0.320/0.641 260 196 270 221
3x120rm+70rm 37wire

19 wire
1.2

1.1
2.2 38.2 4912 1898 0.153/0.286 0.253/0.443 295 223 305 257
3x150rm+70rm 37wire

19 wire
1.4
1.1
2.3 42.1 5673 2334 0.124/0.286 0.206/0.443 330 249 350 292
3x185rm+95rm 37wire

19 wire
1.6

1.1
2.5 47.3 7105 2831 0.0991/0.193 0.164/0.320 385 282 410 337
3x240rm+120rm 37/61 wire

19 wire
1.7
1.2
2.7 53.8 9219 3601 0.0754/0.153 0.125/0.253 425 327 470 400
3x300rm+120rm 61 wire

37 wire
1.8
1.4
2.9 58.6 11563 4387 0.0601/0.124 0.100/0.206 478 368 584 455
3x400rm+185rm 61 wire

37 wire
2.0

1.6
3.4 71.4 14007 5299 0.047/0.0991 0.0778/0.164 590 459 700 544
Note: As per customer requirement we shall provide Fire proof/resistant cables (16 mm2 to 300 mm2) which can resist fire temperature of 750C with circuit integrity. Also we shall provide Fiber glass wrapping XLPE insulated cables (35 mm2 to 400 mm2) whose max. operating conductor temperature is 155°C without short circuit & Insulation life is almost double.

Members of :