Type : 2XRGY / A2XRGY / YJV32

Voltage : 600 / 1000 V (permissible Service Voltage : 720 / 1200 V)

Special Type

  • 2XRGY(FP*)/2XRGY(FG*)
  • 2XRGY-FR/A2XRGY-FR
  • 2XRGY-FRLS/A2XRGY-FRLS
  • 2XRGY-LSZH/A2XFRGY-LSZH
  • 2XRGY/A2XRGY-HRFR-150°

Specifications / Rating

ASTM: B-3
BDS IEC: 60228&60502-1
VDE: 0271
IEC: 60331&584
IS: 7098-1 & BS: 5467

Applications

  • Indoor
  • Outdoor
  • Underground
  • Ship Power
  • Power plant
  • Switch gear
  • Generator
  • Industrial

Construction : Annealed Copper or Aluminium Conductor / XLPE Insulation / PVC inner sheath / Round galv, Steel strip armoured / PVC outer sheath.

tecnical data
Cross Sectional Area No. & Approx. Diameter of wire Cu/Al Nominal Thickness of Insulation Diameter of round armour wire Nominal Thickness of Sheath Overall diameter (approx) Approx Weight of Cable Max. DC resist. of conductor at 20°C Current rating at 30°C in ground Current rating at 35°C in air
Cu Al Cu Al Cu Al Cu Al
Core x mm2 No./mm mm mm mm mm Kg/Km Kg/Km ohm/km ohm/km amps amps amps amps
3×25 rm+16 rm 7/19 wire

7 wire
0.9
0.7
1.6 1.8 27.5 1919 1337 0.717/1.15 1.2/1.91 130 94 120 96
3×35 sm+16 rm 19 wire

7 wire
0.9
0.7
1.6 1.8 29.3 2363 1596 0.524/1.15 0.868/1.91 155 114 150 117
3×50 sm+25 rm 19 wire

7/19 wire
1.0
0.9
1.6 2.0 31.9 3105 1995 0.387/0.727 0.641/1.20 190 133 190 142
3×70 sm+35 rm 19 wire

19 wire
1.1
0.9
2.0 2.1 37.9 4153 2595 0.286/0.524 0.443/0.868 225 164 230 179
3×95 sm+50 rm 19 wire

19 wire
1.1
1.0
2.0 2.2 42.1 5372 3251 0.193/0.387 0.320/0.641 260 196 270 221
3×120 rm+70 rm 37wire

19 wire
1.2

1.1
2.0 2.4 45.8 6921 4197 0.153/0.286 0.253/0.443 295 223 305 257
3×150 sm+70 rm 37wire

19 wire
1.4
1.1
2.5 2.5 50.2 8070 4772 0.124/0.286 0.206/0.443 330 249 350 292
3×185 sm+95 rm 37wire

19 wire
1.6

1.1
2.5 2.7 55.1 9655 5543 0.0991/0.193 0.164/0.320 385 282 410 337
3×240 sm+120 rm 37/61 wire

19 wire
1.7

1.2
2.5 2.9 61.1 11952 6618 0.0754/0.153 0.125/0.253 425 327 470 400
3×300 sm+150 rm 61 wire

37 wire
1.8

1.4
2.5 3.1 67.0 14563 7837 0.0601/0.124 0.100/0.206 578 368 664 455
Note: As per customer requirement we shall provide Fire proof/resistant cables (16 mm2 to 300 mm2) which can resist fire temperature of 750C with circuit integrity. Also we shall provide Fiber glass wrapping XLPE insulated cables (35 mm2 to 300 mm2) whose max. operating conductor temperature is 180°C without short circuit & Insulation life is almost double.