Type : 2XHSY / A2XHSY

Voltage : 6 / 10 (12 KV) (Permissible Service Voltage : 6.35 / 11 KV)

Special Type

  • 2XHSY-1 (FP) FR
  • 2XHSY-1 (FRLS)
  • 2XHSY-1(LSZH)
  • 2XHSY-1-HRFR-105°C

Specifications / Rating

ASTM: B-3
BDS IEC: 60228 & 60502-2
IEC: 60228 & 60502-2
IS: 7098-2

Applications

  • Indoor
  • Outdoor
  • Underground
  • In water
  • Power plant
  • Switch gear
  • Generator
  • Industrial
  • Substation

Construction : Annealed Copper or Aluminium Conductor / Inner semiconducting layer / XLPE Insulation / Outer semiconducting layer / Metallic screen / PVC outer sheath.

tecnical data
Nominal Conductor Area Nominal Thickness of Insulation Nominal Thickness of Sheath Overall diameter (approx) Approx Weight of Cable Max. DC resist. of conductor at 20°C Current rating in ground at 20°C Current rating in air at 30°C
Cu Al Cu Al Cu Al Cu Al
Core x mm2 mm mm mm Kg/Km Kg/Km ohm/km ohm/km amps amps amps amps
1x25rm 3.4 1.8 22.0 630 471 0.727 1.200 155 121 160 125
1x35rm 3.4 1.8 23.0 750 532 0.524 0.868 191 148 190 148
1x50rm 3.4 1.8 24.2 890 579 0.387 0.641 226 176 229 178
1x70rm 3.4 1.8 25.8 1140 704 0.268 0.443 280 218 285 222
1x95rm 3.4 1.8 27.6 1430 838 0.193 0.320 332 258 350 272
1x120rm 3.4 1.8 29.0 1640 892 0.153 0.253 378 294 410 319
1x150rm 3.4 1.8 30.5 1950 1050 0.124 0.206 425 330 468 363
1x185rm 3.4 1.9 32.5 2350 1197 0.0991 0.164 480 373 542 421
1x240rm 3.4 2.0 35.0 2940 1444 0.0754 0.125 554 430 640 487
1x300rm 3.4 2.0 37.2 3570 1700 0.0601 0.100 625 485 732 567
1x400rm 3.4 2.1 40.7 4430 1937 0.0470 0.0778 716 557 850 661
1x500rm 3.4 2.2 43.6 5520 2397 0.0366 0.0605 792 616 978 761
1x630rm 3.4 2.3 47.7 7000 3064 0.0283 0.0479 902 710 1130 878
1x800rm 3.4 2.5 52.0 9020 3999 0.0221 0.0367 970 753 1290 1001
1x1000rm 3.4 2.6 56.2 11100 4836 0.0176 0.0291 1040 809 1435 1116

Note For value of Capacitance, Inductance & AC Resistance please refer to page no. 88 in this catalogue.

Members of :