Type : NYCY / YCY / NYCWY
Voltage : 600 / 1000 V (permissible Service Voltage : 720 / 1200 V)
Special Type
- NYCY(FP) / NYCY(FG)
- NYCY-FR / NAYCY-FR
- NYCY-FRLS / NYCY-FRLS
- NYCY-LSZH / NYCY-LSZH
- NYCY-HRFR-150°
Specifications / Rating
ASTM: B-3
BDS IEC: 60228&60502-1
VDE: 0271
IEC: 60331&584
IS: 1554-1&BS: 6346
Applications
- Indoor
- Outdoor
- Underground
- In water
- Steel lighting
- AC Survo motor
- VH motor
Construction : Annealed Copper or Aluminium Conductor / PVC Insulation / Concentric copper conductor / PVC outer Sheath.
Cross Sectional Area | No. & Approx. Diameter of wire Cu/Al | No & dia of concentric conductor | Nominal Thickness of Insulation | Nominal Thickness of Sheath | Overall diameter (approx) | Approx Weight of Cable | Max. DC resist. of conductor at 20°C | Current rating at 30°C in ground | Current rating at 35°C in air | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Core x mm2 | No./mm | No./mm | mm | mm | mm | Kg/Km | ohm/km | amps | amps | ||||
3×25 rm+16 rm | 7/2.14 | 80/0.50 | 1.2 | 1.8 | 24.3 | 1302 | 0.717/1.15 | 110 | 86 | ||||
3×35 sm+16 rm | 19 wire |
80/0.50 | 1.2 | 1.8 | 26.2 | 1623 | 0.524/1.15 | 130 | 120 | ||||
3×50 sm+25 rm | 19 wire |
50/0.80 | 1.4 | 1.9 | 30.4 | 2266 | 0.387/0.727 | 155 | 150 | ||||
3×70 sm+35 rm | 19 wire |
70/0.80 | 1.4 | 2.1 | 33.7 | 3011 | 0.286/0.524 | 190 | 190 | ||||
3×95 sm+50 rm | 19 wire |
59/1.05 | 1.6 | 2.2 | 38.4 | 4005 | 0.193/0.387 | 225 | 230 | ||||
3×120 rm+70 rm | 37wire |
71/1.13 | 1.6 | 2.4 | 42.1 | 5031 | 0.153/0.286 | 260 | 270 | ||||
3×150 sm+70 rm | 37wire |
71/1.13 | 1.8 | 2.5 | 45.3 | 6013 | 0.124/0.286 | 295 | 305 | ||||
3×185 sm+95 rm | 37wire |
67/1.35 | 2.0 | 2.7 | 50.1 | 7458 | 0.0991/0.193 | 330 | 350 | ||||
3×240 sm+120 rm | 37/61 wire |
67/1.53 | 2.2 | 2.9 | 55.8 | 9497 | 0.0754/0.153 | 385 | 410 | ||||
3×300 sm+150 rm | 61 wire |
80/1.56 | 2.4 | 3.2 | 61.3 | 11730 | 0.0601/0.124 | 425 | 470 | ||||
3×400 srm+185 rm | 61 wire |
81/1.71 | 2.6 | 3.4 | 76.3 | 15815 | 0.047/0.0991 | 480 | 530 | ||||
Note: As per customer requirement we shall provide Fire proof/resistant cables (16 mm2 to 300 mm2) which can resist fire temperature of 750C with circuit integrity. Also we shall provide Fiber glass wrapping PVC insulated cables (35 mm2 to 400 mm2) whose max. operating conductor temperature is 155°C without short circuit & Insulation life is almost double. |