Type : NYYf
Voltage : 600 / 1000 V (permissible Service Voltage : 720 / 1200 V)
Special Type
- NYYF(FP)/NYYF(FG)
- NYYF-FRLS
- NYYF-LSZH
- NYYF-HRFR-150°
Specifications / Rating
ASTM : B-3
BDS IEC : 60228&60502-1
VDE : 0271
IEC : 60331
IS : 1554-1
Applications
- BatteryConnection
- Magnetic Crane
- Underground
- Welding
- Power plant
- Switch gear
- Generator
- Industrial


Construction : Annealed Flexible Copper Conductor / PVC Insulation / PVC inner sheath / Black PVC outer sheath
Single Core
Cross Sectional Area | No. & Maximum Diameter of wire Cu / Al | Nominal Thickness of Insulation | Nominal Thickness of Sheath | Approx Overall Diameter | Approx Weight of Conductor | Max. Dc resist. of conductor at 20°C | Current rating at 35°C |
---|---|---|---|---|---|---|---|
Core x mm2 | No | mm | mm | mm | Kg/Km | ohm/km | amps |
1×4 rm | 53/0.31 | 1.0 | 1.8 | 8.5 | 105 | 4.95 | 41 |
1×6 rm | 80/0.31 | 1.0 | 1.8 | 9.1 | 135 | 3.3 | 52 |
1×10 rm | 76/0.41 | 1.0 | 1.8 | 10.2 | 185 | 1.91 | 72 |
1×16 rm | 122/0.41 | 1.0 | 1.8 | 11.8 | 260 | 1.21 | 98 |
1×25 rm | 190/0.41 | 1.2 | 1.8 | 13.6 | 370 | 0.78 | 131 |
1×35 rm | 266/0.41 | 1.2 | 1.8 | 15.2 | 480 | 0.554 | 167 |
1×50 rm | 379/0.41 | 1.4 | 1.8 | 17.6 | 668 | 0.386 | 204 |
1×70 rm | 343/0.41 | 1.4 | 1.8 | 19.2 | 880 | 0.272 | 256 |
1×95 rm | 465/0.41 | 1.6 | 1.8 | 21.8 | 1160 | 0.206 | 314 |
1×120 rm | 588/0.41 | 1.6 | 1.8 | 24.0 | 1420 | 0.161 | 366 |
1×150 rm | 735/0.41 | 1.8 | 1.8 | 26.5 | 1772 | 0.129 | 423 |
Two Core
Cross Sectional Area | No. & Maximum Diameter of wire Cu / Al | Nominal Thickness of Insulation | Nominal Thickness of Sheath | Approx Overall Diameter | Approx Weight of Conductor | Max. Dc resist. of conductor at 20°C | Current rating at 35°C | |||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Core x mm2 | No | mm | mm | mm | Kg/Km | ohm/km | amps | |||||
2×4 rm | 53/0.31 | 1.0 | 1.8 | 13.8 | 290 | 4.95 | 37 | |||||
2×6 rm | 80/0.31 | 1.0 | 1.8 | 15.2 | 375 | 3.3 | 48 | |||||
2×10 rm | 76/0.41 | 1.0 | 1.8 | 16.9 | 502 | 1.91 | 66 | |||||
2×16 rm | 122/0.41 | 1.0 | 1.8 | 19 | 700 | 1.21 | 90 | |||||
2×25 rm | 190/0.41 | 1.2 | 1.8 | 22.4 | 1060 | 0.78 | 121 | |||||
2×35 rm | 266/0.41 | 1.2 | 2.0 | 24.7 | 1360 | 0.554 | 154 | |||||
Note: As per customer requirement we shall provide Fire proof/resistant cables (4 mm2 to 150 mm2) which can resist fire temperature of 750C with circuit integrity. Also we shall provide Fiber glass wrapping PVC insulated cables (35 mm2 to 150 mm2) whose max. operating conductor temperature is 155°C without short circuit & Insulation life is almost double. |