Type : NYYF
Voltage : 600 / 1000 V (permissible Service Voltage : 720 / 1200 V)
Special Type
- NYYF(FP)/NYYF(FG)
- NYYF-FRLS
- NYYF-LSZH
- NYYF-HRFR-150°
Specifications / Rating
ASTM : B-3
BDS IEC : 60228&60502-1
VDE : 0271
IEC : 60331
IS : 1554-1
Applications
- Magnet Crane
- Outdoor
- Underground
- Hysteresis
- Power plant
- Switch gear
- Generator
- Industrial


Construction : Annealed Flexible Copper Conductor / PVC Insulation / PVC inner sheath / Black PVC outer sheath
Three Core
Cross Sectional Area | No. & Maximum Diameter of wire Cu / Al | Nominal Thickness of Insulation | Nominal Thickness of Sheath | Approx Overall Diameter | Approx Weight of Conductor | Max. Dc resist. of conductor at 20°C | Current rating at 35°C |
---|---|---|---|---|---|---|---|
Core x mm2 | No | mm | mm | mm | Kg/Km | ohm/km | amps |
3×4 rm | 53/0.31 | 1.0 | 1.8 | 14.6 | 350 | 4.95 | 33 |
3×6 rm | 80/0.31 | 1.0 | 1.8 | 18.0 | 450 | 3.3 | 43 |
3×10 rm | 76/0.41 | 1.0 | 1.8 | 18.0 | 630 | 1.91 | 58 |
3×16 rm | 122/0.41 | 1.0 | 1.8 | 20.4 | 940 | 1.21 | 78 |
3×25 rm | 190/0.41 | 1.2 | 1.8 | 25.4 | 1320 | 0.78 | 102 |
3×35 rm | 266/0.41 | 1.2 | 2.0 | 28.5 | 1750 | 0.554 | 125 |
Four Core
Cross Sectional Area | No. & Maximum Diameter of wire Cu / Al | Nominal Thickness of Insulation | Nominal Thickness of Sheath | Approx Overall Diameter | Approx Weight of Conductor | Max. Dc resist. of conductor at 20°C | Current rating at 35°C | |||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Core x mm2 | No | mm | mm | mm | Kg/Km | ohm/km | amps | |||||
4×4 rm | 53/0.31 | 1.0 | 1.8 | 16.6 | 424 | 4.95 | 33 | |||||
4×6 rm | 80/0.31 | 1.0 | 1.8 | 18.4 | 530 | 3.3 | 43 | |||||
4×10 rm | 76/0.41 | 1.0 | 1.8 | 20.7 | 750 | 1.91 | 58 | |||||
4×16 rm | 122/0.41 | 1.0 | 1.8 | 25.0 | 1145 | 1.21 | 78 | |||||
4×25 rm | 190/0.41 | 1.2 | 1.8 | 29.5 | 1690 | 0.78 | 102 | |||||
4×35 rm | 266/0.41 | 1.2 | 2.0 | 32.8 | 2150 | 0.554 | 125 | |||||
Note: As per customer requirement we shall provide Fire proof/resistant cables (4 mm2 to 150 mm2) which can resist fire temperature of 750C with circuit integrity. Also we shall provide ethylene propylene rubber (EPR) insulated flexible cables. |