Type : 2XSEYY / A2XSE

Voltage : 18 / 30 (36 KV) (Permissible Service Voltage : 19/33 KV)

Special Type

  • 2XSEYY- FR
  • 2XSEYY- FRLS
  • 2XSEYY- LSZH
  • 2XSEYY- HRFR-105°C

Specifications / Rating

ASTM: B-3
BDS IEC: 60228 & 60502-2
IEC: 60228 & 60502-2
IS: 7098-2

Applications

  • Indoor
  • Outdoor
  • Underground
  • In water
  • Power plant
  • Switch gear
  • Generator
  • Industrial
  • Substation

Construction : Annealed Copper or Aluminium Conductor / Inner semiconducting layer / XLPE Insulation / Outer semiconducting layer / Metallic screen / Separation sheath / PVC outer sheath.

tecnical data
Nominal Conductor Area Nominal Thickness of Insulation Nominal Thickness of Sheath Approx overall dia. of cable Approx Weight of Cable Max. DC resist. of conductor at 20°C Current rating in ground at 20°C Current rating in air at 30°C
Cu Al Cu Al Cu Al Cu Al
Core x mm2 mm mm mm Kg/Km Kg/Km ohm/km ohm/km amps amps amps amps
3x50rm 8.0 3.1 76.0 6200 5256 0.3870 0.641 222 172 223 173
3x70rm 8.0 3.2 80.0 7310 5988 0.2680 0.443 274 213 276 215
3x95rm 8.0 3.3 84.0 8520 6726 0.1930 0.320 329 256 339 263
3x120rm 8.0 3.4 87.0 9420 7154 0.153 0.253 368 286 385 299
3x150rm 8.0 3.5 91.0 10625 7792 0.1240 0.206 417 324 443 344
3x185rm 8.0 3.6 95.0 12190 8696 0.0991 0.164 462 359 511 397
3x240rm 8.0 3.8 100.0 14450 9918 0.0754 0.125 534 415 589 457
3x300rm 8.0 4.0 105.0 16975 11309 0.0601 0.100 575 446 620 481

Note: For value of Capacitance, Inductance & AC Resistance please refer to page no. 88 in this Catalogue.