Type : 2XSEYFGY / A2XSEYFGY

Voltage : 6/10 (12) K; Permissible Service Voltage : 6.35/11KV

Special Type

  • 2XSEYFGY- FR
  • 2XSEYFGY- FRLS
  • 2XSEYFGY- LSZH
  • 2XSEYFGY- HRFR-105°C

Specifications / Rating

ASTM: B-3
BDS IEC: 60228 & 60502-2
IEC: 60228 & 60502-2
IS: 7098-2

Applications

  • Indoor
  • Outdoor/Shore
  • Underground
  • In salt water
  • Power plant
  • Switch gear
  • Generator
  • Industrial
  • Substation

Construction : Annealed Copper or Aluminium Conductor / Inner semiconducting layer / XLPE Insulation / Outer semiconducting layer / Metallic screen / Separation sheath / Flat steel wire armour with helical tape / PVC outer sheath.

tecnical data
Nominal Conductor Area Nominal Thickness of Insulation Nominal dia. of flat steel wire armour Nominal Thickness of Sheath Approx overall dia. of cable Approx Weight of Cable Max. DC resist. of conductor at 20°C Current rating in ground at 20°C Current rating in air at 30°C
Cu Al Cu Al Cu Al Cu Al
Core x mm2 mm mm mm mm Kg/Km Kg/Km ohm/km ohm/km amps amps amps amps
3x16rm 3.4 4×0.8 2.0 44.0 3200 2895 1.150 1.910 120 93 125 97
3x25rm 3.4 4×0.8 2.2 47.5 3460 2977 0.7270 1.200 145 113 147 114
3x35rm 3.4 4×0.8 2.3 50.5 4020 3359 0.5240 0.868 182 141 183 112
3x50rm 3.4 4×0.8 2.4 53.5 4630 3686 0.3870 0.641 218 169 218 169
3x70rm 3.4 4×0.8 2.6 57.0 5570 4248 0.2680 0.443 269 209 270 210
3x95rm 3.4 4×0.8 2.7 61.5 6765 4971 0.1930 0.320 324 252 333 259
3x120rm 3.4 4×0.8 2.8 65.0 7750 5484 0.153 0.253 362 282 378 294
3x150rm 3.4 4×0.8 2.9 68.0 8830 5957 0.1240 0.206 411 319 436 338
3x185rm 3.4 4×0.8 3.0 72.5 10320 6826 0.0991 0.164 455 354 503 391
3x240rm 3.4 4×0.8 3.2 77.5 12470 7938 0.0754 0.125 527 409 580 450
3x300rm 3.4 4×0.8 3.3 83.0 14900 9234 0.0601 0.100 567 440 611 474
3x400rm 3.4 4×0.8 3.6 90.0 18500 10945 0.0601 0.100 600 466 745 579

Note: For value of Capacitance, Inductance & AC Resistance please refer to page no. 88 in this Catalogue.